www.advantech.com/products Online Download Ordering Information ƒ ƒ ADAM-4118 Robust 8-ch Thermocouple Input Module w/ Modbus ƒ ƒ ADAM-4150 Robust 15-ch Digital I/O Module with Modbus ƒ ƒ ADAM-4168 Robust 8-ch Relay Output Module with Modbus Specifications General ƒ ƒ Power Consumption 0.5W @ 24 VDC Analog Input ƒ ƒ Channels 8 differential and independent configuration channels ƒ ƒ Input Impedance Voltage: 20 MΩ Current: 120 Ω ƒ ƒ Input Type T/C, mV, V, mA ƒ ƒ Input Range Thermocouple J 0 ~ 760°C R 500 ~ 1,750°C K 0 ~ 1,370°C S 500 ~ 1,750°C T -100 ~ 400°C B 500 ~ 1,800°C E 0 ~ 1,000°C Voltage mode ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current mode ±20 mA, 4 ~ 20 mA ƒ ƒ Accuracy Voltage mode: ±0.1% or better Current mode: ±0.2% or better ƒ ƒ Resolution 16-bit ƒ ƒ Sampling Rate 10/100 samples/sec (selected by Utility) ƒ ƒ CMR @ 50/60 Hz 92 dB ƒ ƒ NMR @ 50/60 Hz 60 dB ƒ ƒ Overvoltage Protection ±60 VDC ƒ ƒ High Common Mode 200 VDC ƒ ƒ Span Drift ±25 ppm/°C (Typical) ƒ ƒ Zero Drift ±6μV/°C ƒ ƒ Built-in TVS/ESD Protection ƒ ƒ Burn-out Detection ADAM-4118 ADAM-4118 ADAM-4150 ADAM-4168 Robust 8-ch Thermocouple Input Module with Modbus Robust 15-ch Digital I/O Module with Modbus Robust 8-ch Relay Output Module with Modbus ADAM-4150 ADAM-4168 Specifications General ƒ ƒ Power Consumption 0.7 W @ 24 VDC Digital Input ƒ ƒ Channels 7 ƒ ƒ Input Level Dry contact: Logic level 0: Close to GND Logic level 1: Open Wet contact: Logic level 0: 3 V max Logic level 1: 10 ~ 30 V (Note: The Digital Input Level 0 and 1 status can be inverted) ƒ ƒ Supports 3 kHz Counter Input (32-bit + 1-bit overflow) ƒ ƒ Supports 3 kHz Frequency Input ƒ ƒ Supports Invert DI Status ƒ ƒ Over Voltage Protection 40 VDC Digital Output ƒ ƒ Channels 8, open collector to 40 V (0.8A max. load) ƒ ƒ Power Dissipation 1W load max ƒ ƒ RON Maximum 150 mΩ ƒ ƒ Supports 1 kHz Pulse Output ƒ ƒ Supports High-to-Low Delay Output ƒ ƒ Supports Low-to-High Delay Output Specifications General ƒ ƒ Power Consumption 1.8 W @ 24 VDC Relay Output ƒ ƒ Output Channels 8 Form A ƒ ƒ Contact Rating 0.5 A @ 120 VAC (Resistive) 0.25 A @ 240 VAC 1 A @ 30 VDC 0.3 A @ 110 VDC ƒ ƒ Breakdown Voltage 750 VAC (50/60 Hz) ƒ ƒ Initial Insulation 1 G Ω min. @ 500 VDC Resistance ƒ ƒ Relay Response On: 3ms Time (Typical) Off: 1ms ƒ ƒ Total Switching Time 10 ms ƒ ƒ Supports 100 Hz pulse output ƒ ƒ Maximum Operating 50 operations/min Speed (at related load) Common Specifications General ƒ ƒ Power Input Unregulated 10 ~ 48 VDC ƒ ƒ Watchdog Timer System (1.6 second) & Communication ƒ ƒ Connector 2 x plug-in terminal blocks (#14 ~ 22 AWG) ƒ ƒ Isolation Voltage 3,000 VDC ƒ ƒ Supported Protocols ASCII Command and Modbus/RTU Environment ƒ ƒ Operating Humidity 5 ~ 95% RH ƒ ƒ Operating Temperature -40 ~ 85°C (-40 ~ 185°F) ƒ ƒ Storage Temperature -40 ~ 85°C (-40 ~ 185°F) RoHS COMPLIANT 2002/95/EC RoHS COMPLIANT 2002/95/EC RoHS COMPLIANT 2002/95/EC Power & Energy Automation 8 5 4 4 10 Panel PCs 9 iDoor Technology Modules 8 Industrial monitors 7 Industrial IoT Gateways 6 Control Cabinet PCs High-Performance Control Panels Industrial Operator Panels 3 2 IntelligentMotionControl andMachineVision 1 11 Control IPCs 12 Remote DA&C Systems 13 Wireless IoT Sensing Devices 14 15 RS-485 I/O Modules 16 Thin-Client Terminals Industrial Ethernet Solutions 17 IP Gateway and Serial Device Servers iNetworking 18 19 WebAccess+ Solution Ethernet I/O Modules Chapter 16 Table of Contents Table of Contents