Ethernet I/O Modules: ADAM-6000 ADAM-6015 Specifications Analog Input Channels 7 (differential) Input Impedance > 10 MΩ Input Connections 2 or 3 wire Input Type Pt, Balco and Ni RTD RTD Types and Temperature Ranges Pt 100 -50°C ~ 150°C 0°C ~ 100°C 0°C ~ 200°C 0°C ~ 400°C -200°C ~ 200°C Pt 1000 -40°C ~ 160°C Supports both IEC 60751 ITS90 (0.0385 W/W/°C) and JIS C 1604 (0.0392 W/W/°C) Balco 500 -30°C ~ 120°C Ni 518 -80°C ~ 100°C 0°C ~ 100°C Accuracy ± 0.1 % or better High speed mode ±0.5% or better Span Drift ± 25 ppm/°C Zero Drift ± 6 μV/°C Resolution 16-bit Sampling Rate 10 sample/ second (total) High speed mode:1K sample/second (total) CMR @ 50/60 HZ 90dB NMR @ 50/60 HZ 60dB * high speed mode does not support CMR/NMR Wire Burn-out Detection Ordering Information ADAM-6015 7-ch Isolated RTD Input Modbus TCP Module 7-ch Isolated RTD Input Modbus TCP Module 8-ch Isolated Analog Input Modbus TCP Module with 2-ch DO 8-ch Isolated Thermocouple Input Modbus TCP Module with 8-ch DO ADAM-6015 ADAM-6017 ADAM-6018 ADAM-6017 Specifications Analog Input Channels 8 (differential) Input Impedance > 10 MΩ (voltage) 120 Ω (current) lnput Type mV, V, mA lnput Range ±150mV , ±500mV , ±1 V , ±5V , ±10V, 0 ~ 150mV, 0 ~ 500mV , 0 ~ 1V , 0 ~ 5V , 0 ~ 10V, 0 ~ 20mA , 4 ~ 20mA , ±20mA Accuracy ±0.1% (voltage) ±0.2% (current) Span Drift ±25 ppm/°C Zero Drift ±6 μV/°C Resolution 16-bit Sampling Rate 10 or 100 sample/ second (total) CMR @ 50/60 HZ 90dB NMR @ 50/60 HZ 67dB Common-Mode 350VDC Voltage Digital Output Channels 2, open collector to 30 V, 100 mA max. load Power Dissipation 300 mW for each module Output Delay On: 100μs Off: 150μs Ordering Information ADAM-6017 8-ch Isolated AI with 2-ch DO Modbus TCP Module ADAM-6018 Specifications Analog Input Channels 8 (differential) Input Impedance > 10 MΩ lnput Type Thermocouple Thermocouple Type and Range: J 0 ~ 760°C R 500 ~ 1,750°C K 0 ~ 1,370°C S 500 ~ 1,750°C T -100 ~ 400°C B 500 ~ 1,800°C E 0 ~ 1,000°C Accuracy ±0.1% Span Drift ±25 ppm/°C Zero Drift ±6 μV/°C Resolution 16-bit Sampling Rate 10 sample/ second (total) CMR @ 50/60 HZ 90dB NMR @ 50/60 HZ 60dB Wire Burn-out Detection Digital Output Channels 8, open collector to 30 V, 100 mA max. load Power Dissipation 300 mW for each module Ordering Information ADAM-6018 8-ch Isolated Thermocouple Input Modbus TCP Module w/ 8-ch DO Common Specifications General LAN 10/100Base-T(X) Power Consumption 2.5 W @ 24 VDC (ADAM-6015) 2.7 W @ 24 VDC (ADAM-6017) 2 W @ 24 VDC (ADAM-6018) Connectors 1 x RJ-45 (LAN), Plug-in screw terminal block (I/O and power) Watchdog System (1.6 second) and Communication (programmable) Power Input 10 ~ 30 VDC Supports Peer-to-Peer Supports GCL Supports Modbus/TCP, TCP/IP, UDP and HTTP Protocols Protection Over Voltage ±35 VDC Protection Isolation Protection 2,000 VDC Built-in TVS/ESD Protection Power Reversal Protection Environment Operating -10 ~ 70°C (14 ~ 158°F) Temperature -20 ~ 70°C (-4 ~ 158°F) (ADAM-6017) Storage Temperature -20 ~ 80°C (-4 ~ 176°F) -30 ~ 80°C (-22 ~ 176°F) (ADAM-6017) Operating Humidity 20 ~ 95% RH (non-condensing) Storage Humidity 0 ~ 95% RH (non-condensing) RoHS COMPLIANT 2002/95/EC RoHS COMPLIANT 2002/95/EC RoHS COMPLIANT 2002/95/EC Chapter 15 Table of Contents Table of Contents