4-14 www. m oxa. com MGate™ MB3660 Series 4 Industrial Ethernet Gateways Industrial Ethernet Gateways > Specifications Modbus Gateway with Power and Ethernet Redundancy For a complicated Modbus system, redundancy is extremely important. The MGate MB3660 Modbus gateways support redundancy for both the power input and Ethernet connection. The MGate MB3660 gateways come with dual AC or DC power inputs built-in for power redundancy, and have dual Ethernet ports (with different IPs) for network redundancy. To accomodate different types of applications, the dual Ethernet ports can be configured in one of two ways: 1. Use the same IP for both Ethernet ports. In this case, the MGate MB3660 gateway will automatically switch to the backup LAN when the main LAN fails. 2. Use different IP addresses for each of the two Ethernet ports. Ethernet Interface Protocols: Modbus TCP Client/Server Number of Ports: 2 (2 IP addresses) Speed: 10/100 Mbps, Auto MDI/MDIX Connector: RJ45 x 2 Serial Interface Protocols: Modbus RTU/ASCII Master/Slave Number of Ports: MGate MB3660-8: 8 MGate MB3660I-8: 8 MGate MB3660-16:16 Serial Standards: RS-232/422/485, software selectable Connectors: DB9 male RS-485 Data Direction Control: ADDC® (automatic data direction control) Isolation Protection: 2 kV (for “-I” model) Serial Communication Parameters Data Bits: 7, 8 Stop Bits: 1, 2 Parity: None, Even, Odd, Space, Mark Flow Control: RTS/CTS, DTR/DSR, RTS Toggle (RS-232 only) Baudrate: 50 bps to 921.6 Kbps Serial Signals RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND RS-422: Tx+, Tx-, Rx+, Rx-, GND RS-485-4w: Tx+, Tx-, Rx+, Rx-, GND RS-485-2w: Data+, Data-, GND Software Configuration Options: Web console, Serial console, Telnet console Utility: Device Search Utility (DSU) for Windows 95, 98, ME, NT, 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2 Network Protocols: TCP/IP, UDP, HTTP, SMTP, NTP, DNS, DHCP Client, SNMPv1 (read only), ARP, Telnet, Radius Multi-master and Multi-drop: Master mode: 128 TCP slaves/servers Slave mode: 256 TCP masters/clients Physical Characteristics Fault Relay Circuit: 3-pin circuit with current carrying capacity of 2 A @ 30 VDC External Storage Drive: SD card for configuration backup Housing: Metal, IP30 Weight: MGate MB3660-8-2AC: 2,731 g (6.02 lb) MGate MB3660-8-2DC: 2,684 g (5.92 lb) MGate MB3660I-8-2AC: 2,753 g (6.07 lb) MGate MB3660-16-2AC: 2,830 g (6.24 lb) MGate MB3660-16-2DC: 2,780 g (6.13 lb) Dimensions: Without ears: 440 x 45 x 198 mm (17.32 x 1.77 x 7.80 in) With ears: 480 x 45 x 198 mm (18.90 x 1.77 x 7.80 in) Environmental Limits Operating Temperature: 0 to 60°C (32 to 140°F) Storage Temperature: -40 to 85°C (-40 to 185°F) Ambient Relative Humidity: 5 to 95% (non-condensing) Vibration: IEC 60068-2-6, IEC 60068-2-64 Shock: IEC 60068-2-27 Drop: IEC 60068-2-32 Power Requirements Input Voltage: For DC models: Dual 20 to 60 VDC (1.5 kV isolation) For AC models: Dual 100 to 240 VAC, 47 to 63 Hz Input Current: MGate MB3660-8-2AC: 144 mA @ 110 VAC; 101 mA @ 220 VAC MGate MB3660-8-2DC: 312 mA @ 24 VDC; 156 mA @ 48 VDC MGate MB3660I-8-2AC: 244 mA @ 110 VAC; 159 mA @ 220 VAC MGate MB3660-16-2AC: 178 mA @ 110 VAC; 120 mA @ 220 VAC MGate MB3660-16-2DC: 390 mA @ 24 VDC; 195 mA @ 48 VDC Power Connector: Terminal block (for DC models) Standards and Certifications Safety: UL 60950-1, EN 60950-1 (LVD) EMC: EN 55022/24 EMI: CISPR 22, FCC Part 15B Class A EMS: IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10V/m IEC 61000-4-8 PFMF MTBF (mean time between failures) Time: MGate MB3660-8-2AC: 716,647 hrs MGate MB3660-8-2DC: 706,783 hrs MGate MB3660I-8-2AC: 224,851 hrs MGate MB3660-16-2AC: 487,416 hrs MGate MB3660-16-2DC: 482,835 hrs Standard: Telcordia SR332 Warranty Warranty Period: 5 years Details: See www.moxa.com/warranty