Programmable RTU Controllers > 15 ioPAC 8600 Series Modules Programmable RTU Controllers 15-10 www. m oxa. com 86M-5250-T: 2 CAN ports, channel LED Power Requirements Input Voltage: 24 to 110 VDC (16.8 to 154 VDC) Environmental Limits Operating Temperature: -40 to 75°C (-40 to 176°F) Storage Temperature: -40 to 85°C (-40 to 185°F) Ambient Relative Humidity: 5 to 95% (non-condensing) Shock: IEC 60068-2-27 Vibration: IEC 60068-2-6 Standards and Certifications Safety: UL 508 EMC: EN 55022/24 EMI: FCC Part 15 Subpart B Class A, CISPR 22 EMS: IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1000 MHz: 3 V/m 1400 MHz to 2100 MHz: 3 V/m 2100 MHz to 2700 MHz: 1 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV (L-PE), 1 kV (L-L); Signal: 1 kV (L-L), 2 kV (L-PE) IEC 61000-4-6 CS: 3 V IEC 61000-4-8 PFMF: 3 A/m Rail Traffic: EN 50155 (essential compliance*), EN 50121-3-2, EN 50121-4 *Moxa defines “essential compliance” to include those EN 50155 requirements that make products more suitable for rolling stock railway applications. Warranty Warranty Period: 5 years Details: See www.moxa.com/warranty Common Specifications Serial Communication Interface: 2 CAN ports Isolation: To system: 3k VDC or 2k Vrms CAN Bus Communication Protocols: CAN 2.0A CAN 2.0B CANopen DS301, V4.02 CANopen DS401 Speed: 10/20/50/125/250/500/800 kbps, 1 Mbps Termination Resistor: N/A, 120 ohms (by DIP) Physical Characteristics Connector: DB9 male Channel LED: Yes Environmental Limits Operating Temperature: -40 to 75°C (-40 to 176°F) Power Requirements Input Current: 60 mA @ 24 VDC MTBF (mean time between failures) Time: 3,306,609 hrs Standard: Telcordia SR332 86M-5212U-T 86M-5250 ioPAC 8600-CPU10-M12-C-T ioPAC 8600-CPU10-RJ45-C-T ioPAC 8600-PW10-15W