16-19 www.mo xa .c o m Smart Remote I/O > ioLogik E2200 Series Remote Automation 16 ioLogik E2214 Specifications ioLogik E2240 Specifications Inputs and Outputs Digital Inputs: 6 channels Relay Outputs: 6 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN or PNP) and Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: open Wet Contact (DI to GND): • On: 0 to 3 VDC • Off: 10 to 30 VDC Common Type: 3 points per COM Counter Frequency: 900 Hz Digital Filtering Time Interval: Software Configurable Relay Output Type: Form A (N.O.) power relay Inputs and Outputs Analog Inputs: 8 channels Analog Outputs: 2 channels Analog Input Isolation: 3k VDC or 2k Vrms Type: Differential input Resolution: 16 bits I/O Mode: Voltage/Current (software selectable) Input Range: ±150 mV, ±500 mV, ±5 V, ±10 V, 0 to 20 mA, 4 to 20 mA Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C Sampling Rate: All channels: • 10 samples/sec for voltage • 6 samples/sec for current Per channel: • 1.25 samples/sec for voltage • 0.75 samples/sec for current Contact Current Rating: • Inductive Load: 2 A @ 30 VDC, 250 VAC, 110 VAC • Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC Minimum permitted load: 1 A @ 5 VDC Initial Insulation Resistance: 1000 mega-ohms (min.) @ 500 VDC Mechanical Endurance: 1,000,000 operations Electrical Endurance: 100,000 operations @ 5 A resistive load Contact Resistance: 100 milli-ohms (max.) Pulse Output: 0.3 Hz at rated load Note: Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik E2214 may malfunction when operating in high condensation environments below 0° Celsius. Power Requirements Input Voltage: 12 to 36 VDC Input Current: 170 mA @ 24 VDC MTBF (mean time between failures) Time: 307,239 hrs Database: Telcordia SR332 Single channel: • 1.25 samples/sec for voltage • 0.75 samples/sec for current Input Impedance: 900 kilo-ohms ohms (min.) Built-in Resistor for Current Input: 120 ohms Analog Output Resolution: 12 bits Output Range: 0 to 10 V, 4 to 20 mA Drive Voltage: 15 VDC for current output Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C Load Resistor: Less than 250 ohms Power Requirements Input Voltage: 12 to 36 VDC Input Current: 190 mA @ 24 VDC MTBF (mean time between failures) Time: 155,941 hrs Standard: Telcordia SR332 ioLogik E2242 Specifications Inputs and Outputs Configurable DIOs (by software): 12 channels Analog Inputs: 4 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN or PNP) and Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: Open Wet Contact (DI to GND): • On: 0 to 3 VDC • Off: 10 to 30 VDC Common Type: 6 points per COM Isolation: 3k VDC or 2k Vrms Counter Frequency: 900 Hz Digital Filtering Time Interval: Software selectable Digital Output Type: Sink I/O Mode: DO or Pulse Output Pulse Output Frequency: 1 kHz Over-Voltage Protection: 45 VDC Over-Current Protection: 2.6 A (4 channels @ 650 mA) Over-Temperature Shutdown: 175°C (min.) Current Rating: 200 mA per channel Analog Input Type: Differential input Resolution: 16 bits I/O Mode: Voltage / Current (software selectable) Input Range: ±150 mV, 0 to 150 mV, ±500 mV, 0 to 500 mV, ±5 V, 0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA