17-8 www. m oxa. com Remote I/O > ioLogik E1200 Series Remote I/O 17 ioLogik E1214 Specifications Inputs and Outputs Digital Inputs: 6 channels Relays: 6 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN or PNP), Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: open Wet Contact (DI to COM): • On: 10 to 30 VDC • Off: 0 to 3 VDC Common Type: 6 points per COM Counter Frequency: 250 Hz Digital Filtering Time Interval: Software configurable Relay Type: Form A (N.O.) power relay Contact Current Rating: Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC Breakdown Voltage: 500 VAC Relay On/Off Time: 1500 ms (max.) Initial Insulation Resistance: 1000 mega-ohms (min.) @ 500 VDC Mechanical Endurance: 5,000,000 operations Electrical Endurance: 100,000 operations @ 5 A resistive load Contact Resistance: 100 milli-ohms (max.) Pulse Output: 0.3 Hz at rated load Note: Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik E1214 may malfunction when operating in high condensation environments below 0°C. Power Requirements Input Voltage: 12 to 36 VDC Input Current: 188 mA @ 24 VDC MTBF (mean time between failures) Time: 808,744 hrs Standard: Telcordia SR332 Inputs and Outputs Analog Inputs: 8 channels Isolation: 3k VDC or 2k Vrms Analog Input Type: Differential input Resolution: 16 bits I/O Mode: Voltage / Current (jumper selectable) Input Range: 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA (burnout detection) Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C ioLogik E1240 Specifications Sampling Rate: • All channels: 12 samples/sec • Per channel: 1.5 samples/sec • Only one channel enabled: 12 samples/sec Input Impedance: 10 mega-ohms (min.) Built-in Resistor for Current Input: 120 ohms Power Requirements Input Voltage: 12 to 36 VDC Input Current: 121 mA @ 24 VDC MTBF (mean time between failures) Time: 474,053 hrs Standard: Telcordia SR332 Inputs and Outputs Digital Inputs: 8 channels Digital Outputs: 4 channels Configurable DIOs (by jumper): 4 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN or PNP), Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: open Wet Contact (DI to COM): • On: 10 to 30 VDC • Off: 0 to 3 VDC Common Type: 12 points per COM Counter Frequency: 250 Hz Digital Filtering Time Interval: Software configurable Digital Output Type: Source I/O Mode: DO or Pulse Output Pulse Output Frequency: 500 Hz Over-Voltage Protection: 41 VDC Over-current Protection: 1.5 A per channel @ 25°C Over-Temperature Shutdown: 175°C (typical), 150°C (min.) Current Rating: 500 mA per channel Power Requirements Output Voltage Rating: 15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4 DO channels) Input Voltage: 12 to 36 VDC Input Current: 130 mA @ 24 VDC MTBF (mean time between failures) Time: 715,256 hrs Standard: Telcordia SR332 ioLogik E1213 Specifications ioLogik E1241 Specifications Inputs and Outputs Analog Outputs: 4 channels Isolation: 3k VDC or 2k Vrms Analog Output Resolution: 12 bits Output Range: 0 to 10 VDC, 4 to 20 mA Drive Voltage: 10 mA (max.) Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C Load Resistor: Internal register, 400 ohms Note: 24 V of external power required when loading exceeds 1000 ohms.