17-9 www.mo xa .c o m Remote I/O > ioLogik E1200 Series Remote Automation 17 ioLogik E1242 Specifications Inputs and Outputs Digital Inputs: 4 channels Configurable DIOs (by jumper): 4 channels Analog Inputs: 4 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN or PNP), Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: open Wet Contact (DI to COM): • On: 10 to 30 VDC • Off: 0 to 3 VDC Common Type: 4 points per COM Counter Frequency: 250 Hz Digital Filtering Time Interval: Software Configurable Digital Output Type: Sink I/O Mode: DO or Pulse Output Pulse Output Frequency: 500 Hz Over-Voltage Protection: 45 VDC Over-Current Protection: 2.6 A (4 channels @ 650 mA) Over-Temperature Shutdown: 175°C (typical), 150°C (min.) Current Rating: 200 mA per channel Analog Input Type: Differential input Resolution: 16 bits I/O Mode: Voltage / Current (jumper selectable) Input Range: 0 to 10 VDC, 0 to 20 mA, 4 to 20 mA, 4 to 20 mA (burnout detection) Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C ±0.5% FSR @ -40 and 75°C Sampling Rate: • All channels: 12 samples/sec • Per channel: 3 samples/sec • Only one channel enabled: 12 samples/sec Input Impedance: 10 mega-ohms (min.) Built-in Resistor for Current Input: 120 ohms Power Requirements Input Voltage: 12 to 36 VDC Input Current: 139 mA @ 24 VDC MTBF (mean time between failures) Time: 502,210 hrs Standard: Telcordia SR332 ioLogik E1262 Specifications Inputs and Outputs Thermocouples: 8 channels Isolation: 3k VDC or 2k Vrms Thermocouple Sensor Type: J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C) Millivolt Type: • Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV • Fault and over-voltage protection: -35 to +35 VDC (power off) -25 to +30 VDC (power on) Sampling Rate: • All channels: 12 samples/sec • Per channel: 1.5 samples/sec • Only one channel enabled: 12 samples/sec Resolution: 16 bits Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C Input Impedance: 10 mega-ohms Power Requirements Input Voltage: 12 to 36 VDC Input Current: 118 mA @ 24 VDC MTBF (mean time between failures) Time: 631,418 hrs Standard: Telcordia SR332 ioLogik E1260 Specifications Inputs and Outputs RTDs: 6 channels Isolation: 3k VDC or 2k Vrms RTD Sensor Type: • PT50, PT100, PT200, PT500 (-200 to 850°C) • PT1000 (-200 to 350°C) • Resistance of 310, 620, 1250, and 2200 ohms Input Connection: 2- or 3-wire Sampling Rate: • All channels: 12 samples/sec • Per channel: 2 samples/sec • Only one channel enabled: 12 samples/sec Resolution: 0.1°C or 0.1 ohm Accuracy: ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C Input Impedance: 625 kilo-ohms Power Requirements Input Voltage: 12 to 36 VDC Input Current: 110 mA @ 24 VDC MTBF (mean time between failures) Time: 660,260 hrs Standard: Telcordia SR332 Power Requirements Input Voltage: 12 to 36 VDC Input Current: 194 mA @ 24 VDC MTBF (mean time between failures) Time: 888,656 hrs Standard: Telcordia SR332