16-18 www. m oxa. com Smart Remote I/O > ioLogik E2200 Series Smart Remote I/O 16 Push Technology for Events and Alarms The ioLogik E2200 series is designed for use with the Moxa’s MX-AOPC UA server. When used with MX-AOPC UA Server, the E2200 is upgraded to use active push communications when communicating state changes and/or events to the SCADA system. Unlike a polling system, when using a push architecture for communications with the SCADA messages will only be delivered when state changes or configured events occur. Active messaging thus allows for big increases in data acquisition and control throughput while also delivering big reductions in network overhead. ioLogik E2210 Specifications Inputs and Outputs Digital Inputs: 12 channels Digital Outputs: 8 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN), Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: open Wet Contact (DI to GND): • On: 0 to 3 VDC • Off: 10 to 30 VDC Common Type: 12 points per COM Counter Frequency: 900 Hz Digital Filtering Time Interval: Software Configurable Digital Output Type: Sink I/O Mode: DO or Pulse Output Pulse Output Frequency: 1 kHz Over-Voltage Protection: 45 VDC Over-Current Protection: 2.6 A (4 channels @ 650 mA) Over-Temperature Shutdown: 175°C (min.) Current Rating: 200 mA per channel Power Requirements Input Voltage: 12 to 36 VDC Input Current: 190 mA @ 24 VDC MTBF (mean time between failures) Time: 213,673 hrs Database: Telcordia SR332 ioLogik E2212 Specifications Inputs and Outputs Digital Inputs: 8 channels Digital Outputs: 8 channels Configurable DIOs: 4 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN or PNP) and Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: open Wet Contact (DI to GND): • On: 0 to 3 VDC • OFF: 10 to 30 VDC Common Type: 6 points per COM Counter Frequency: 900 Hz Digital Filtering Time Interval: Software Configurable Digital Output Type: Sink I/O Mode: DO or Pulse Output Pulse Output Frequency: 1 kHz Over-Voltage Protection: 45 VDC Over-Current Protection: 2.6 A (4 channels @ 650 mA) Over-Temperature Shutdown: 175°C (min.) Current Rating: 200 mA per channel Power Requirements Input Voltage: 12 to 36 VDC Input Current: 136 mA @ 24 VDC MTBF (mean time between failures) Time: 217,722 hrs Database: Telcordia SR332