16-11 www.mo xa .c o m Smart Remote I/O > ioLogik W5340-HSPA Remote Automation 16 Specifications LAN Ethernet: 1 10/100 Mbps RJ45 port, with up to 3 ioLogik E1200 units daisy-chained Protection: 1.5 kV magnetic isolation Protocols: Modbus/TCP (slave), TCP/IP, UDP, DHCP, BOOTP, SNMP, SNTP Serial Interface: 1 RS-232/422/485 (software selectable) DB9 male or terminal block port Parity: None, Odd, Even, Space, Mark Data Bits: 5, 6, 7, 8 Stop Bits: 1, 2 Flow Control: None, Hardware, XON/XOFF Baudrate: 300 to 115200 bps Protocols: Modbus/RTU (master/gateway), serial tunnel mode (client/ server) Inputs and Outputs Configurable DIOs (by software): 8 channels Relays: 2 channels Analog Inputs: 4 channels Isolation: 3k VDC or 2k Vrms Digital Input Sensor Type: Wet Contact (NPN or PNP), Dry Contact I/O Mode: DI or Event Counter Dry Contact: • On: short to GND • Off: open Wet Contact (DI to GND): • On: 0 to 3 VDC • Off: 10 to 30 VDC Common Type: 4 points per COM Counter Frequency: 900 Hz Digital Filtering Time Interval: Software configurable Digital Output Type: Sink I/O Mode: DO or Pulse Output Pulse Output Frequency: 1 kHz Over-Voltage Protection: 45 VDC Over-Current Protection: 2.6 A (4 channels @ 650 mA) Over-Temperature Shutdown: 160°C (min.) Current Rating: 200 mA per channel DIO Output Leakage Current: 3.6 mA @ 24 VDC Relay Type: Form A (N.O.) power relay Contact Current Rating: Resistive Load: 1 A @ 30 VDC, 250 VAC, 110 VAC Initial Insulation Resistance: 1000 micro-ohms (min.) @ 500 VDC Mechanical Endurance: 5,000,000 operations Electrical Endurance: 600,000 operations @ 1 A resistive load Contact Resistance: 100 milli-ohms (max.) Pulse Output: 0.3 Hz at rated load Note: Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik W5340-HSPA may malfunction when operating in high condensation environments below 0° Celsius. Analog Input Type: Differential input Resolution: 16 bits I/O Mode: Voltage / Current (software selectable) Input Range: 0 to 10 V, ±10 V, ±5 V, 0 to 20 mA, 4 to 20 mA Accuracy: • ±0.1% FSR @ 25°C • ±0.3% FSR @ -30 and 70°C Sampling Rate: All channels: 32 samples/sec Per channel: 8 samples/sec Single channel: 100 samples/sec Input Impedance: 200k ohms (min.) Built-in Resistor for Current Input: 120 ohms Power Requirements Input Voltage: 12 to 36 VDC Input Current: 196 mA @ 24 VDC Physical Characteristics Wiring: I/O cable, 14 AWG (max.) Dimensions: 46.8 x 135 x 105 mm (1.84 x 5.31 x 4.13 in) Weight: 495 g (1.09 lb) Mounting: DIN rail (standard), wall (optional) Storage Expansion Slot: Up to 32 GB SD™ memory card (SD 2.0 compatible) Note: For units operating in extreme temperatures, industrial-grade, wide temperature SD cards are required. Environmental Limits Operating Temperature: Standard Models: -10 to 55°C (14 to 131°F) Wide Temp. Models: -30 to 70°C (-22 to 158°F) Storage Temperature: -40 to 85°C (-40 to 185°F) Ambient Relative Humidity: 5 to 95% (non-condensing) Shock: IEC 60068-2-27 Vibration: IEC 60068-2-6 Altitude: Up to 2000 m Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes. Standards and Certifications Safety: UL 508, EN 60950-1 EMC: EN 55022/24 EMI: CISPR 22, FCC Part 15B Class A EMS: IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV IEC 61000-4-6 CS: Signal: 3 V/m IEC 61000-4-8 Magnetic Field: 1 A/m Radio: R&TTE: EN 301 489-1, EN 301 489-7, EN 301 489-24, EN 301 511, EN 301 908-1; NCC Green Product: RoHS, CRoHS, WEEE Note: Please check Moxa’s website for the most up-to-date certification status. MTBF (mean time between failures) Time: 280,739 hrs Standard: Telcordia SR332 Warranty Warranty Period: 2 years* Details: See www.moxa.com/warranty *Because of the limited lifetime of power relays, products that use that component are covered by a 2-year warranty.