17-27 www.mo xa .c o m Remote I/O > ioLogik 4000 Expansion Modules Remote Automation 17 M-2600: 16 digital outputs, sink type, 24 VDC, 0.3 A Digital Outputs: 16 channels Type: sink Output Range: 24 VDC nominal On-state Voltage Drop: 0.3 VDC @ 25°C (max.) On-state Current: 1 mA per channel (min.) Off Leakage Current: 50 μA (max.) Current Rating: 0.5 A per channel Common Type: 8 channels per external common (single common) Input Current: 60 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O flat cable 20-pin MTBF: 9,732,360 hrs (Standard: Telcordia SR332) M-3802: 8 analog inputs, 4 to 20 mA, 12 bits Analog Inputs: 8 channels Resolution in Ranges: 12 bits, 3.91 μA/bit Input Current Range: 4 to 20 mA (single-ended) Data Format: 16-bit integer (2’s complement) Accuracy: • ±0.1%, FSR @ 25°C • ±0.3%, FSR @ 0°C, 60°C Input Impedance: 120 ohms Conversion Time: 4 ms for all channels Input Current: 80 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O cable max. 14 AWG MTBF: 7,375,920 hrs (Standard: Telcordia SR332) M-4402: 4 analog outputs, 4 to 20 mA, 12 bits Analog Outputs: 4 channels Resolution in Ranges: 12 bits, 3.91 μA/bit Output Current Range: 4 to 20 mA (single-ended) Data Format: 16-bit integer (2’s complement) Accuracy: • ±0.1%, FSR @ 25°C • ±0.3%, FSR @ 0°C, 60°C Output Impedance: 500 ohms (max.) Conversion Time: 2 ms for all channels Input Current: 60 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O cable max. 14 AWG MTBF: 7,840,200 hrs (Standard: Telcordia SR332) M-2601: 16 digital outputs, source type, 24 VDC, 0.3 A Digital Outputs: 16 channels Type: source Output Range: 24 VDC nominal On-state Voltage Drop: 0.3 VDC @ 25°C (max.) On-state Current: 1 mA per channel (min.) Off Leakage Current: 50 μA (max.) Current Rating: 0.5 A per channel Common Type: 8 channels per external common (single common) Input Current: 60 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O flat cable 20-pin MTBF: 9,749,880 hrs (Standard: Telcordia SR332) M-3810: 8 analog inputs, 0 to 10 V, 12 bits Analog Inputs: 8 channels Resolution in Ranges: 12 bits, 2.44 mV/bit Input Current Range: 0 to 10 VDC (single-ended) Data Format: 16-bit integer (2’s complement) Accuracy: • ±0.1%, FSR @ 25°C • ±0.3%, FSR @ 0°C, 60°C Input Impedance: 500 kilo-ohms Conversion Time: 4 ms for all channels Input Current: 60 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O cable max. 14 AWG MTBF: 7,288,320 hrs (Standard: Telcordia SR332) M-4410: 4 analog outputs, 0 to 10 V, 12 bits Analog Outputs: 4 channels Resolution in Ranges: 12 bits, 2.44 mV/bit Output Current Range: 0 to 10 VDC (single-ended) Data Format: 16-bit integer (2’s complement) Accuracy: • ±0.1%, FSR @ 25°C • ±0.3%, FSR @ 0°C, 60°C Output Impedance: 5 kilo-ohms (max.) Conversion Time: 2 ms for all channels Input Current: 60 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O cable max. 14 AWG MTBF: 6,219,600 hrs (Standard: Telcordia SR332) Analog Input Modules Analog Output Modules M-6200: 2 analog inputs, RTD: PT100, JPT100 RTDs: 2 channels Sensor Types: • PT50, PT100, PT200, PT500, PT1000 (resistance 100 milli-ohms/bit) • JPT100, JPT200, JPT500, JPT1000 (resistance 10 milli-ohms/bit) • NI100, NI200, NI500, NI1000, NI120, CU10 (resistance 20 milli-ohms/ bit) Resolution: 0.1°C per 10 milli-ohms Data Format: 16-bit integer (2’s complement) Accuracy: • ±0.1%, FSR @ 25°C • ±0.3%, FSR @ 0°C, 60°C Input Impedance: 500 kilo-ohms Conversion Time: 200 ms for all channels Diagnostics: Range over (if range over, data=Dx8000) Input Current: 80 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O cable max. 14 AWG MTBF: 3,644,160 hrs (Standard: Telcordia SR332) M-6201: 2 analog inputs, thermocouple Thermocouples: 2 channels Sensor Types: Type J/K/T/E/R/S/B/N/L/U/C/D (mV input 10 μV/bit, 2 μV/bit) Resolution: 0.1°C/10 μV Data Format: 16-bit integer (2’s complement) Accuracy: • ±0.1%, FSR @ 25°C • ±0.3%, FSR @ 0°C, 60°C Input Impedance: 500 kilo-ohms Conversion Time: 200 ms for all channels Diagnostics: Range over (if range over, data=Dx8000) Input Current: 80 mA @ 5 VDC Isolation: I/O to logic (photocoupler isolation) Wiring: I/O cable max. 14 AWG MTBF: 3,828,120 hrs (Standard: Telcordia SR332) Temperature Input Modules